Hudson View Care Center Inc.
Survey Date: Tuesday, June 10, 2014
Survey Type: Fire Safety
Deficiency: K0071 (Properly constructed linen or trash chutes.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, August 7, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 10, 2014
Survey Type: Fire Safety
Deficiency: K0021 (Exit doors that are held open by devices that will automatically close on the activation of a fire a)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, August 7, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 10, 2014
Survey Type: Health
Deficiency: F0332 (Keep the rate of medication errors (wrong drug, wrong dose, wrong time) to less than 5%.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, August 7, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 10, 2014
Survey Type: Fire Safety
Deficiency: K0072 (Exits that are free from obstructions and can be used at all times.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, August 7, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 10, 2014
Survey Type: Fire Safety
Deficiency: K0130 (Other fire safety features required by fire safety codes.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, August 7, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 10, 2014
Survey Type: Fire Safety
Deficiency: K0056 (An approved automatic sprinkler system connected to the fire alarm system.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, August 7, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 19, 2013
Survey Type: Fire Safety
Deficiency: K0018 (Corridor and hallway doors that block smoke.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 19, 2013
Survey Type: Fire Safety
Deficiency: K0211 (Properly installed hallway dispensers for alcohol-based hand rub.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 19, 2013
Survey Type: Fire Safety
Deficiency: K0104 (Proper construction of ducts through walls designed to prevent smoke passage.)
Scope Severity Code: B
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 19, 2013
Survey Type: Fire Safety
Deficiency: K0034 (Exit stairways and towers that are smoke proof.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 19, 2013
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 19, 2013
Survey Type: Health
Deficiency: F0285 (Coordinate assessments with the pre-admission screening and resident review program for mentally-ill)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 19, 2013
Survey Type: Fire Safety
Deficiency: K0056 (An approved automatic sprinkler system connected to the fire alarm system.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 19, 2013
Survey Type: Health
Deficiency: F0371 (Store, cook, and serve food in a safe and clean way.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 19, 2013
Survey Type: Fire Safety
Deficiency: K0045 (Proper backup exit lighting.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, November 15, 2012
Survey Type: Health
Deficiency: F0278 (Ensure each resident receives an accurate assessment by a qualified health professional.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, January 24, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a complaint inspection)
Survey Date: Thursday, November 15, 2012
Survey Type: Health
Deficiency: F0280 (Allow residents the right to participate in the planning or revision of care and treatment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, January 24, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a complaint inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Health
Deficiency: F0333 (Ensure that residents are safe from serious medication errors.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Fire Safety
Deficiency: K0048 (A written emergency evacuation plan.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Health
Deficiency: F0282 (Provide care by qualified persons according to each resident's written plan of care.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Fire Safety
Deficiency: K0104 (Proper construction of ducts through walls designed to prevent smoke passage.)
Scope Severity Code: B
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Health
Deficiency: F0313 (Ensure that residents receive proper treatment and assistive devices to maintain their vision and he)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Health
Deficiency: F0428 (At least once a month, have a licensed pharmacist review each resident's medication (s) and report a)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Health
Deficiency: F0248 (Provide activities to meet the interests and needs of each resident.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Health
Deficiency: F0280 (Allow residents the right to participate in the planning or revision of care and treatment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Fire Safety
Deficiency: K0020 (Proper stairway enclosures and vertical shafts.)
Scope Severity Code: B
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Health
Deficiency: F0309 (Provide necessary care and services to maintain or improve the highest well being of each resident .)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Health
Deficiency: F0329 (Ensure that each resident's 1) entire drug/medication regimen is free from unnecessary drugs; and 2))
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Health
Deficiency: F0279 (Develop a complete care plan that meets all the resident's needs, with timetables and actions that c)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Health
Deficiency: F0332 (Keep the rate of medication errors (wrong drug, wrong dose, wrong time) to less than 5%.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Health
Deficiency: F0325 (Ensure residents maintain acceptable nutritional status.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, June 19, 2012
Survey Type: Fire Safety
Deficiency: K0076 (Proper medical gas storage and administration areas.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 10, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)