Survey Date: Thursday, October 17, 2013
Survey Type: Fire Safety
Deficiency: K0072 (Exits that are free from obstructions and can be used at all times.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, November 14, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, October 17, 2013
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, November 14, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, October 17, 2013
Survey Type: Fire Safety
Deficiency: K0050 (Record of quarterly fire drills for each shift under varying conditions.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, November 14, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, October 17, 2013
Survey Type: Fire Safety
Deficiency: K0047 (Properly located and lighted "Exit" signs.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, November 14, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, October 17, 2013
Survey Type: Fire Safety
Deficiency: K0062 (Automatic sprinkler systems that have been maintained in working order.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, November 14, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Sunday, September 29, 2013
Survey Type: Health
Deficiency: F0457 (Provide bedrooms that hold no more than 4 residents per room.)
Scope Severity Code: B
Deficiency Corrected: Waiver Has Been Granted
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Sunday, September 29, 2013
Survey Type: Health
Deficiency: F0309 (Provide necessary care and services to maintain or improve the highest well being of each resident .)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, November 1, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Sunday, September 29, 2013
Survey Type: Health
Deficiency: F0329 (Ensure that each resident's 1) entire drug/medication regimen is free from unnecessary drugs; and 2))
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, November 1, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Sunday, September 29, 2013
Survey Type: Health
Deficiency: F0241 (Provide care for residents in a way that maintains or improves their dignity and respect in full rec)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, November 1, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Sunday, September 29, 2013
Survey Type: Health
Deficiency: F0278 (Ensure each resident receives an accurate assessment by a qualified health professional.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, November 1, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Sunday, September 29, 2013
Survey Type: Health
Deficiency: F0253 (Provide housekeeping and maintenance services.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, November 1, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Sunday, September 29, 2013
Survey Type: Health
Deficiency: F0314 (Give residents proper treatment to prevent new bed (pressure) sores or heal existing bed sores.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, November 1, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Sunday, September 29, 2013
Survey Type: Health
Deficiency: F0425 (Provide routine and emergency drugs through a licensed pharmacist and only under the general supervi)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, November 1, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Sunday, June 24, 2012
Survey Type: Fire Safety
Deficiency: K0141 (No-smoking signs where oxygen is used.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, July 10, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Sunday, June 24, 2012
Survey Type: Health
Deficiency: F0314 (Give residents proper treatment to prevent new bed (pressure) sores or heal existing bed sores.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, August 8, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Sunday, June 24, 2012
Survey Type: Health
Deficiency: F0156 (Give residents a notice of rights, rules, services and charges.)
Scope Severity Code: B
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, August 8, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Sunday, June 24, 2012
Survey Type: Fire Safety
Deficiency: K0046 (Emergency lighting that can last at least 1 1/2 hours.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, July 10, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Sunday, June 24, 2012
Survey Type: Health
Deficiency: F0457 (Provide bedrooms that hold no more than 4 residents per room.)
Scope Severity Code: B
Deficiency Corrected: Waiver Has Been Granted
Date the deficiency was corrected: Wednesday, August 8, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Sunday, June 24, 2012
Survey Type: Health
Deficiency: F0281 (Ensure services provided by the nursing facility meet professional standards of quality.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, August 8, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Sunday, June 24, 2012
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, July 10, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Sunday, June 24, 2012
Survey Type: Health
Deficiency: F0458 (Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet fo)
Scope Severity Code: D
Deficiency Corrected: Waiver Has Been Granted
Date the deficiency was corrected: Wednesday, August 8, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Sunday, June 24, 2012
Survey Type: Health
Deficiency: F0241 (Provide care for residents in a way that maintains or improves their dignity and respect in full rec)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, August 8, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Sunday, June 24, 2012
Survey Type: Health
Deficiency: F0514 (Keep accurate, complete and organized clinical records on each resident that meet professional stand)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, August 8, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Sunday, June 24, 2012
Survey Type: Fire Safety
Deficiency: K0130 (Other fire safety features required by fire safety codes.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, July 10, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Fire Safety
Deficiency: K0069 (Properly protected cooking facilities.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 4, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Fire Safety
Deficiency: K0046 (Emergency lighting that can last at least 1 1/2 hours.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 4, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Fire Safety
Deficiency: K0025 (Walls that prevent smoke from passing through and would resist fire for at least one hour.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 4, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 4, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 4, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Fire Safety
Deficiency: K0062 (Automatic sprinkler systems that have been maintained in working order.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 4, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Sunday, April 10, 2011
Survey Type: Health
Deficiency: F0502 (Give or get quality laboratory services/tests in a timely manner to meet the needs of residents.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Sunday, April 10, 2011
Survey Type: Health
Deficiency: F0156 (Give residents a notice of rights, rules, services and charges.)
Scope Severity Code: C
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Sunday, April 10, 2011
Survey Type: Health
Deficiency: F0367 (Make sure that special or therapeutic diets are ordered by the attending doctor.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Sunday, April 10, 2011
Survey Type: Health
Deficiency: F0332 (Keep the rate of medication errors (wrong drug, wrong dose, wrong time) to less than 5%.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Sunday, April 10, 2011
Survey Type: Health
Deficiency: F0226 (Develop and implement policies for 1) screening and training employees; and the 2) prevention, ident)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Sunday, April 10, 2011
Survey Type: Health
Deficiency: F0314 (Give residents proper treatment to prevent new bed (pressure) sores or heal existing bed sores.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Sunday, April 10, 2011
Survey Type: Health
Deficiency: F0284 (Develop a post-discharge plan with the resident and family for the resident's care after leaving the)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)