Survey Date: Thursday, August 14, 2014
Survey Type: Fire Safety
Deficiency: K0027 (Smoke barrier doors that can resist smoke for at least 20 minutes.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Tuesday, September 16, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 14, 2014
Survey Type: Fire Safety
Deficiency: K0062 (Automatic sprinkler systems that have been maintained in working order.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Tuesday, September 16, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 14, 2014
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Tuesday, September 16, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 14, 2014
Survey Type: Fire Safety
Deficiency: K0064 (Portable fire extinguishers.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Tuesday, September 16, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 14, 2014
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Tuesday, September 16, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 14, 2014
Survey Type: Fire Safety
Deficiency: K0018 (Corridor and hallway doors that block smoke.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Tuesday, September 16, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 8, 2013
Survey Type: Health
Deficiency: F0332 (Keep the rate of medication errors (wrong drug, wrong dose, wrong time) to less than 5%.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, August 20, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 8, 2013
Survey Type: Fire Safety
Deficiency: K0027 (Smoke barrier doors that can resist smoke for at least 20 minutes.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 8, 2013
Survey Type: Fire Safety
Deficiency: K0144 (Weekly inspections and monthly testing of generators.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Friday, August 9, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 8, 2013
Survey Type: Fire Safety
Deficiency: K0070 (Restrictions on the use of portable space heaters.)
Scope Severity Code: C
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Tuesday, August 20, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 8, 2013
Survey Type: Fire Safety
Deficiency: K0066 (Posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Tuesday, August 20, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 8, 2013
Survey Type: Fire Safety
Deficiency: K0018 (Corridor and hallway doors that block smoke.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 8, 2013
Survey Type: Fire Safety
Deficiency: K0064 (Portable fire extinguishers.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Thursday, August 15, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 8, 2013
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Friday, August 9, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 8, 2013
Survey Type: Fire Safety
Deficiency: K0025 (Walls that prevent smoke from passing through and would resist fire for at least one hour.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Friday, August 31, 2012
Survey Type: Health
Deficiency: F0323 (Ensure that a nursing home area is free from accident hazards and provide adequate supervision to pr)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, September 1, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Thursday, August 16, 2012
Survey Type: Fire Safety
Deficiency: K0012 (Approved construction type or materials.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Thursday, August 23, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 16, 2012
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Thursday, August 23, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 16, 2012
Survey Type: Fire Safety
Deficiency: K0027 (Smoke barrier doors that can resist smoke for at least 20 minutes.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Thursday, August 23, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 16, 2012
Survey Type: Fire Safety
Deficiency: K0076 (Proper medical gas storage and administration areas.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Thursday, August 23, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 16, 2012
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Thursday, August 23, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 16, 2012
Survey Type: Health
Deficiency: F0441 (Have a program that investigates, controls and keeps infection from spreading.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, September 19, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 16, 2012
Survey Type: Health
Deficiency: F0371 (Store, cook, and serve food in a safe and clean way.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, August 16, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 16, 2012
Survey Type: Health
Deficiency: F0465 (Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staf)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, August 23, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 16, 2012
Survey Type: Fire Safety
Deficiency: K0066 (Posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Thursday, August 23, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, February 24, 2012
Survey Type: Health
Deficiency: F0323 (Ensure that a nursing home area is free from accident hazards and provide adequate supervision to pr)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, February 25, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Monday, November 21, 2011
Survey Type: Health
Deficiency: F0309 (Provide necessary care and services to maintain or improve the highest well being of each resident .)
Scope Severity Code: G
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, January 6, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Monday, November 21, 2011
Survey Type: Health
Deficiency: F0272 (Conduct initial and periodic assessments of each resident's functional capacity.)
Scope Severity Code: G
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, January 6, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)