Alden Estates Of Naperville, Inc.
Survey Date: Thursday, July 10, 2014
Survey Type: Health
Deficiency: F0309 (Provide necessary care and services to maintain or improve the highest well being of each resident .)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, July 30, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 10, 2014
Survey Type: Health
Deficiency: F0441 (Have a program that investigates, controls and keeps infection from spreading.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, July 30, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 10, 2014
Survey Type: Health
Deficiency: F0323 (Ensure that a nursing home area is free from accident hazards and provide adequate supervision to pr)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, July 30, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 10, 2014
Survey Type: Health
Deficiency: F0368 (1) Provide 3 meals at regular times; 2) serve breakfast within 14 hours of dinner; and 3) offer a sn)
Scope Severity Code: B
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Wednesday, July 30, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 10, 2014
Survey Type: Health
Deficiency: F0328 (Properly care for residents needing special services, including: injections, colostomy, ureostomy, i)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, July 30, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 9, 2014
Survey Type: Fire Safety
Deficiency: K0076 (Proper medical gas storage and administration areas.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, July 30, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 9, 2014
Survey Type: Fire Safety
Deficiency: K0018 (Corridor and hallway doors that block smoke.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, August 10, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 9, 2014
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, July 30, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 9, 2014
Survey Type: Fire Safety
Deficiency: K0062 (Automatic sprinkler systems that have been maintained in working order.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, July 10, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 9, 2014
Survey Type: Fire Safety
Deficiency: K0033 (Protected exits that allow the resident to escape the building.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, August 10, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 9, 2014
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, July 10, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 9, 2014
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, August 10, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 9, 2014
Survey Type: Fire Safety
Deficiency: K0020 (Proper stairway enclosures and vertical shafts.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, August 10, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 9, 2014
Survey Type: Fire Safety
Deficiency: K0012 (Approved construction type or materials.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, August 10, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 9, 2014
Survey Type: Fire Safety
Deficiency: K0025 (Walls that prevent smoke from passing through and would resist fire for at least one hour.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, August 10, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 2, 2014
Survey Type: Health
Deficiency: F0176 (Allow residents to self-administer drugs if determined safe.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, July 16, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a complaint inspection)
Survey Date: Friday, June 14, 2013
Survey Type: Health
Deficiency: F0226 (Develop and implement policies for 1) screening and training employees; and the 2) prevention, ident)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, July 5, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Friday, June 14, 2013
Survey Type: Health
Deficiency: F0441 (Have a program that investigates, controls and keeps infection from spreading.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, July 5, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Friday, June 14, 2013
Survey Type: Health
Deficiency: F0279 (Develop a complete care plan that meets all the resident's needs, with timetables and actions that c)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, July 5, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 13, 2013
Survey Type: Fire Safety
Deficiency: K0067 (Heating and ventilation systems that have been properly installed according to the manufacturer's in)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 29, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 13, 2013
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 29, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 13, 2013
Survey Type: Fire Safety
Deficiency: K0012 (Approved construction type or materials.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 29, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 13, 2013
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 29, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 13, 2013
Survey Type: Fire Safety
Deficiency: K0025 (Walls that prevent smoke from passing through and would resist fire for at least one hour.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 29, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 13, 2013
Survey Type: Fire Safety
Deficiency: K0045 (Proper backup exit lighting.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 29, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 13, 2013
Survey Type: Fire Safety
Deficiency: K0054 (Properly maintained smoke detectors.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 29, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 13, 2013
Survey Type: Fire Safety
Deficiency: K0033 (Protected exits that allow the resident to escape the building.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 29, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 13, 2013
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 29, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 13, 2013
Survey Type: Fire Safety
Deficiency: K0076 (Proper medical gas storage and administration areas.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 29, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Health
Deficiency: F0328 (Properly care for residents needing special services, including: injections, colostomy, ureostomy, i)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, September 1, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Fire Safety
Deficiency: K0054 (Properly maintained smoke detectors.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, October 7, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Fire Safety
Deficiency: K0020 (Proper stairway enclosures and vertical shafts.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, October 7, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Fire Safety
Deficiency: K0018 (Corridor and hallway doors that block smoke.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, October 7, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Fire Safety
Deficiency: K0144 (Weekly inspections and monthly testing of generators.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, October 7, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Health
Deficiency: F0309 (Provide necessary care and services to maintain or improve the highest well being of each resident .)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, September 1, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Health
Deficiency: F0371 (Store, cook, and serve food in a safe and clean way.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, September 1, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Fire Safety
Deficiency: K0062 (Automatic sprinkler systems that have been maintained in working order.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, October 7, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Health
Deficiency: F0441 (Have a program that investigates, controls and keeps infection from spreading.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, September 1, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, October 7, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Fire Safety
Deficiency: K0067 (Heating and ventilation systems that have been properly installed according to the manufacturer's in)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, October 7, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, October 7, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, August 23, 2012
Survey Type: Health
Deficiency: F0514 (Keep accurate, complete and organized clinical records on each resident that meet professional stand)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, September 1, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Monday, March 12, 2012
Survey Type: Health
Deficiency: F0441 (Have a program that investigates, controls and keeps infection from spreading.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, March 26, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Monday, March 12, 2012
Survey Type: Health
Deficiency: F0157 (Immediately tell the resident, the resident's doctor, and a family member of situations (injury/decl)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, March 26, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Monday, March 12, 2012
Survey Type: Health
Deficiency: F0333 (Ensure that residents are safe from serious medication errors.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, March 26, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Tuesday, December 6, 2011
Survey Type: Health
Deficiency: F0356 (Post nurse staffing information/data on a daily basis.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, December 19, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Tuesday, December 6, 2011
Survey Type: Health
Deficiency: F0312 (Assist those residents who need help with eating/drinking, grooming and personal and oral hygiene.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, December 19, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Tuesday, November 15, 2011
Survey Type: Health
Deficiency: F0323 (Ensure that a nursing home area is free from accident hazards and provide adequate supervision to pr)
Scope Severity Code: G
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, December 5, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)