Survey Date: Tuesday, January 21, 2014
Survey Type: Fire Safety
Deficiency: K0051 (A fire alarm system that can be heard throughout the facility.)
Scope Severity Code: C
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, March 8, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, January 21, 2014
Survey Type: Fire Safety
Deficiency: K0066 (Posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, March 8, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, January 21, 2014
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, March 8, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, January 21, 2014
Survey Type: Fire Safety
Deficiency: K0048 (A written emergency evacuation plan.)
Scope Severity Code: C
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, March 8, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, January 21, 2014
Survey Type: Fire Safety
Deficiency: K0062 (Automatic sprinkler systems that have been maintained in working order.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, March 8, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, January 21, 2014
Survey Type: Fire Safety
Deficiency: K0144 (Weekly inspections and monthly testing of generators.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, March 8, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, January 21, 2014
Survey Type: Fire Safety
Deficiency: K0211 (Properly installed hallway dispensers for alcohol-based hand rub.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, March 8, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, January 21, 2014
Survey Type: Fire Safety
Deficiency: K0076 (Proper medical gas storage and administration areas.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, March 8, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Friday, January 17, 2014
Survey Type: Health
Deficiency: F0280 (Allow residents the right to participate in the planning or revision of care and treatment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, March 3, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Friday, January 17, 2014
Survey Type: Health
Deficiency: F0281 (Ensure services provided by the nursing facility meet professional standards of quality.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, March 3, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Friday, January 17, 2014
Survey Type: Health
Deficiency: F0309 (Provide necessary care and services to maintain or improve the highest well being of each resident .)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, March 3, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Friday, January 17, 2014
Survey Type: Health
Deficiency: F0371 (Store, cook, and serve food in a safe and clean way.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, March 3, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Friday, January 17, 2014
Survey Type: Health
Deficiency: F0325 (Ensure residents maintain acceptable nutritional status.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, March 3, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Friday, January 17, 2014
Survey Type: Health
Deficiency: F0329 (Ensure that each resident's 1) entire drug/medication regimen is free from unnecessary drugs; and 2))
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, March 3, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Friday, January 17, 2014
Survey Type: Health
Deficiency: F0157 (Immediately tell the resident, the resident's doctor, and a family member of situations (injury/decl)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, March 3, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Friday, January 17, 2014
Survey Type: Health
Deficiency: F0406 (Give or get specialized rehabilitative services per the patient's assessment or plan of care.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, March 3, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Monday, June 17, 2013
Survey Type: Health
Deficiency: F0328 (Properly care for residents needing special services, including: injections, colostomy, ureostomy, i)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 8, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a complaint inspection)
Survey Date: Monday, June 17, 2013
Survey Type: Health
Deficiency: F0157 (Immediately tell the resident, the resident's doctor, and a family member of situations (injury/decl)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 8, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a complaint inspection)
Survey Date: Friday, June 15, 2012
Survey Type: Health
Deficiency: F0371 (Store, cook, and serve food in a safe and clean way.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Friday, June 15, 2012
Survey Type: Health
Deficiency: F0353 (Have enough nurses to care for every resident in a way that maximizes the resident's well being.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Friday, June 15, 2012
Survey Type: Health
Deficiency: F0246 (Reasonably accommodate the needs and preferences of each resident.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Friday, June 15, 2012
Survey Type: Health
Deficiency: F0253 (Provide housekeeping and maintenance services.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Friday, June 15, 2012
Survey Type: Health
Deficiency: F0441 (Have a program that investigates, controls and keeps infection from spreading.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Friday, June 15, 2012
Survey Type: Health
Deficiency: F0309 (Provide necessary care and services to maintain or improve the highest well being of each resident .)
Scope Severity Code: G
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Friday, June 15, 2012
Survey Type: Health
Deficiency: F0323 (Ensure that a nursing home area is free from accident hazards and provide adequate supervision to pr)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Friday, June 15, 2012
Survey Type: Health
Deficiency: F0224 (Protect each resident from mistreatment, neglect and misappropriation of personal property.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 13, 2012
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 13, 2012
Survey Type: Fire Safety
Deficiency: K0211 (Properly installed hallway dispensers for alcohol-based hand rub.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 13, 2012
Survey Type: Fire Safety
Deficiency: K0050 (Record of quarterly fire drills for each shift under varying conditions.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 13, 2012
Survey Type: Fire Safety
Deficiency: K0048 (A written emergency evacuation plan.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 13, 2012
Survey Type: Fire Safety
Deficiency: K0064 (Portable fire extinguishers.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 13, 2012
Survey Type: Fire Safety
Deficiency: K0045 (Proper backup exit lighting.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, June 13, 2012
Survey Type: Fire Safety
Deficiency: K0062 (Automatic sprinkler systems that have been maintained in working order.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Saturday, August 4, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, November 17, 2011
Survey Type: Health
Deficiency: F0157 (Immediately tell the resident, the resident's doctor, and a family member of situations (injury/decl)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, December 27, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Thursday, January 27, 2011
Survey Type: Health
Deficiency: F0356 (Post nurse staffing information/data on a daily basis.)
Scope Severity Code: C
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 11, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, January 27, 2011
Survey Type: Health
Deficiency: F0325 (Ensure residents maintain acceptable nutritional status.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 11, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, January 27, 2011
Survey Type: Health
Deficiency: F0371 (Store, cook, and serve food in a safe and clean way.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 11, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, January 27, 2011
Survey Type: Health
Deficiency: F0314 (Give residents proper treatment to prevent new bed (pressure) sores or heal existing bed sores.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 11, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, January 27, 2011
Survey Type: Health
Deficiency: F0225 (1) Hire only people with no legal history of abusing, neglecting or mistreating residents; or 2) rep)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 11, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, January 27, 2011
Survey Type: Health
Deficiency: F0363 (Make sure menus meet the resident's nutritional needs and that there is a prepared menu by which nut)
Scope Severity Code: C
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 11, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, January 27, 2011
Survey Type: Health
Deficiency: F0441 (Have a program that investigates, controls and keeps infection from spreading.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 11, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, January 27, 2011
Survey Type: Health
Deficiency: F0309 (Provide necessary care and services to maintain or improve the highest well being of each resident .)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 11, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, January 27, 2011
Survey Type: Health
Deficiency: F0252 (Provide a safe, clean, comfortable and home-like environment; and allow residents to use personal be)
Scope Severity Code: C
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 11, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, January 27, 2011
Survey Type: Health
Deficiency: F0221 (Keep each resident free from physical restraints, unless needed for medical treatment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 11, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, January 27, 2011
Survey Type: Health
Deficiency: F0242 (Ensure residents have the right to have a choice over activities, their schedules, and health care a)
Scope Severity Code: B
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 11, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0018 (Corridor and hallway doors that block smoke.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, April 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0056 (An approved automatic sprinkler system connected to the fire alarm system.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0069 (Properly protected cooking facilities.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0154 (Back-up procedures in place for a faulty automatic sprinkler system.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0076 (Proper medical gas storage and administration areas.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0130 (Other fire safety features required by fire safety codes.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0052 (An approved installation, maintenance and testing program for fire alarm systems.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, April 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0050 (Record of quarterly fire drills for each shift under varying conditions.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0012 (Approved construction type or materials.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0048 (A written emergency evacuation plan.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, April 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0066 (Posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0155 (An approved back-up procedure for a faulty fire alarm system.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0072 (Exits that are free from obstructions and can be used at all times.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0045 (Proper backup exit lighting.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0144 (Weekly inspections and monthly testing of generators.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, April 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0051 (A fire alarm system that can be heard throughout the facility.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, April 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0064 (Portable fire extinguishers.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, January 26, 2011
Survey Type: Fire Safety
Deficiency: K0017 (Corridors that are separated from use areas by walls constructed to limit the passage of smoke.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, March 18, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)