Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0141 (No-smoking signs where oxygen is used.)
Scope Severity Code: C
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0062 (Automatic sprinkler systems that have been maintained in working order.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0045 (Proper backup exit lighting.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0051 (A fire alarm system that can be heard throughout the facility.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0048 (A written emergency evacuation plan.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0046 (Emergency lighting that can last at least 1 1/2 hours.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0054 (Properly maintained smoke detectors.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0021 (Exit doors that are held open by devices that will automatically close on the activation of a fire a)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0069 (Properly protected cooking facilities.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, June 22, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0025 (Walls that prevent smoke from passing through and would resist fire for at least one hour.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0018 (Corridor and hallway doors that block smoke.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, May 28, 2014
Survey Type: Fire Safety
Deficiency: K0017 (Corridors that are separated from use areas by walls constructed to limit the passage of smoke.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 20, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, May 22, 2014
Survey Type: Health
Deficiency: F0441 (Have a program that investigates, controls and keeps infection from spreading.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, June 12, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, May 22, 2014
Survey Type: Health
Deficiency: F0226 (Develop and implement policies for 1) screening and training employees; and the 2) prevention, ident)
Scope Severity Code: C
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Friday, June 13, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, May 22, 2014
Survey Type: Health
Deficiency: F0356 (Post nurse staffing information/data on a daily basis.)
Scope Severity Code: C
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Thursday, June 12, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, May 22, 2014
Survey Type: Health
Deficiency: F0371 (Store, cook, and serve food in a safe and clean way.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, June 12, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, May 22, 2014
Survey Type: Health
Deficiency: F0333 (Ensure that residents are safe from serious medication errors.)
Scope Severity Code: D
Deficiency Corrected: Past Non-Compliance
Date the deficiency was corrected: Thursday, May 22, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, May 22, 2014
Survey Type: Health
Deficiency: F0431 (Maintain drug records and properly mark/label drugs and other similar products according to accepted)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, June 12, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, May 22, 2014
Survey Type: Health
Deficiency: F0315 (Ensure that each resident who enters the nursing home without a catheter is not given a catheter, un)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, June 12, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, May 22, 2014
Survey Type: Health
Deficiency: F0314 (Give residents proper treatment to prevent new bed (pressure) sores or heal existing bed sores.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, June 12, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, May 22, 2014
Survey Type: Health
Deficiency: F0323 (Ensure that a nursing home area is free from accident hazards and provide adequate supervision to pr)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, June 12, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 27, 2013
Survey Type: Fire Safety
Deficiency: K0069 (Properly protected cooking facilities.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 15, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 27, 2013
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 15, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 27, 2013
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 15, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 27, 2013
Survey Type: Fire Safety
Deficiency: K0048 (A written emergency evacuation plan.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 15, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 27, 2013
Survey Type: Fire Safety
Deficiency: K0018 (Corridor and hallway doors that block smoke.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 15, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 27, 2013
Survey Type: Fire Safety
Deficiency: K0015 (Fire resistant room wall surfaces.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 15, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 27, 2013
Survey Type: Fire Safety
Deficiency: K0062 (Automatic sprinkler systems that have been maintained in working order.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 15, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 27, 2013
Survey Type: Fire Safety
Deficiency: K0050 (Record of quarterly fire drills for each shift under varying conditions.)
Scope Severity Code: C
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 15, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 20, 2013
Survey Type: Health
Deficiency: F0167 (Allow residents to easily view the results of the nursing home's most recent inspection.)
Scope Severity Code: C
Deficiency Corrected: Deficient, Provider Has Plan Of Correction
Date the deficiency was corrected: Tuesday, July 9, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 20, 2013
Survey Type: Health
Deficiency: F0325 (Ensure residents maintain acceptable nutritional status.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, July 9, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 20, 2013
Survey Type: Health
Deficiency: F0329 (Ensure that each resident's 1) entire drug/medication regimen is free from unnecessary drugs; and 2))
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, July 9, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 20, 2013
Survey Type: Health
Deficiency: F0225 (1) Hire only people with no legal history of abusing, neglecting or mistreating residents; or 2) rep)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, July 9, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 20, 2013
Survey Type: Health
Deficiency: F0363 (Make sure menus meet the resident's nutritional needs and that there is a prepared menu by which nut)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, July 9, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 20, 2013
Survey Type: Health
Deficiency: F0441 (Have a program that investigates, controls and keeps infection from spreading.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, July 9, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 20, 2013
Survey Type: Health
Deficiency: F0431 (Maintain drug records and properly mark/label drugs and other similar products according to accepted)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, July 9, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 20, 2013
Survey Type: Health
Deficiency: F0241 (Provide care for residents in a way that maintains or improves their dignity and respect in full rec)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, July 9, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, June 20, 2013
Survey Type: Health
Deficiency: F0371 (Store, cook, and serve food in a safe and clean way.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, July 9, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Friday, November 30, 2012
Survey Type: Health
Deficiency: F0157 (Immediately tell the resident, the resident's doctor, and a family member of situations (injury/decl)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, December 3, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a complaint inspection)
Survey Date: Friday, November 30, 2012
Survey Type: Health
Deficiency: F0328 (Properly care for residents needing special services, including: injections, colostomy, ureostomy, i)
Scope Severity Code: G
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, December 3, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a complaint inspection)
Survey Date: Friday, November 30, 2012
Survey Type: Health
Deficiency: F0314 (Give residents proper treatment to prevent new bed (pressure) sores or heal existing bed sores.)
Scope Severity Code: G
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, December 3, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a complaint inspection)
Survey Date: Friday, September 7, 2012
Survey Type: Health
Deficiency: F0498 (Make sure that nurse aides show they have the skills and techniques to be able to care for residents)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, September 17, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Friday, July 13, 2012
Survey Type: Health
Deficiency: F0159 (Properly hold, secure, and manage each resident's personal money which is deposited with the nursing)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, July 13, 2012
Survey Type: Health
Deficiency: F0371 (Store, cook, and serve food in a safe and clean way.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, July 13, 2012
Survey Type: Health
Deficiency: F0469 (Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, July 13, 2012
Survey Type: Health
Deficiency: F0441 (Have a program that investigates, controls and keeps infection from spreading.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, July 13, 2012
Survey Type: Health
Deficiency: F0329 (Ensure that each resident's 1) entire drug/medication regimen is free from unnecessary drugs; and 2))
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, July 13, 2012
Survey Type: Health
Deficiency: F0323 (Ensure that a nursing home area is free from accident hazards and provide adequate supervision to pr)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0027 (Smoke barrier doors that can resist smoke for at least 20 minutes.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0017 (Corridors that are separated from use areas by walls constructed to limit the passage of smoke.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, March 18, 2014
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0154 (Back-up procedures in place for a faulty automatic sprinkler system.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0046 (Emergency lighting that can last at least 1 1/2 hours.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0012 (Approved construction type or materials.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0025 (Walls that prevent smoke from passing through and would resist fire for at least one hour.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0050 (Record of quarterly fire drills for each shift under varying conditions.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0067 (Heating and ventilation systems that have been properly installed according to the manufacturer's in)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0155 (An approved back-up procedure for a faulty fire alarm system.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0062 (Automatic sprinkler systems that have been maintained in working order.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0018 (Corridor and hallway doors that block smoke.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0052 (An approved installation, maintenance and testing program for fire alarm systems.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Thursday, July 12, 2012
Survey Type: Fire Safety
Deficiency: K0054 (Properly maintained smoke detectors.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 15, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)